Home › Wire Size Calculator
Wire size for a run — by amps, one-way distance and voltage, sized to keep voltage drop within 3%.
No cost line here — this one is geometry / sizing, not a material quantity. Cost depends on the material and installer you choose.
Required circular mils = (2 × K × Amps × Distance in ft) ÷ (3% × Voltage) · K = 12.9 for copper, 21.2 for aluminum · Pick the next standard AWG size up
20 A over 100 ft at 120 V on copper: (2 × 12.9 × 20 × 100) ÷ 3.6 = 14,333 circular mils → 8 AWG, with an actual drop of 3.13 V (2.6%).
3% on a branch circuit is the common design target (5% total for feeder plus branch). This calculator sizes for 3% — a guideline, not a code rule.
No — oversizing only costs more and is harder to bend. Undersizing causes voltage drop, dim lights and hot insulation, so always round up to the next size.
No — the wire must also have the ampacity for the breaker protecting it. Ampacity tables and local code / the NEC make the final call, and a licensed electrician should verify any real installation.