Home › CFM Calculator
Exhaust fan size for a room — the CFM the fan needs to move, from the room's volume and how many air changes per hour that kind of room wants.
No cost line here — this one is geometry / sizing, not a material quantity. Cost depends on the material and installer you choose.
Room volume (cu ft) = Length × Width × Ceiling height · CFM = volume × air changes per hour ÷ 60 · Typical air-change guidance: bathroom 8 · kitchen 6 · bedroom 4 · living area 2 · basement 3 · garage 6
A 10 × 12 ft bathroom with an 8 ft ceiling has a volume of 10 × 12 × 8 = 960 cu ft. At 8 air changes per hour: 960 × 8 ÷ 60 = 128 CFM — so choose a fan rated at about 130 CFM or more.
How many times a fan replaces the room's entire volume of air in one hour. A bathroom at 8 air changes per hour clears steam and odour quickly; a living area at 2 just keeps the air fresh. The rates in this calculator are typical guidance — except where a code sets a minimum, as it does for bathroom exhaust.
Yes, in most codes: 50 CFM for intermittent (switched) exhaust or 20 CFM for continuous exhaust is the common reference figure. A small bathroom often lands on that minimum; a large one with a separate shower and soaking tub needs the air-changes figure, which is what this calculator works out — treat the result as a sizing estimate and check your local code.
The rating is measured on a test rig with no duct attached. A long duct run, elbows, a restrictive wall cap and a dirty grille all add static pressure and cut the real airflow — sometimes by a third or more. Short, smooth, straight ducting gets you closest to the rated figure, and sizing with a little headroom is normal.