Voltage drop for a wire run — pick the wire size and see the drop in volts and percent, and whether it stays within the usual 3% guideline.

Type your numbers — the result updates live.

No cost line here — this one is geometry / sizing, not a material quantity. Cost depends on the material and installer you choose.

Formula

Voltage drop (V) = (2 × K × Amps × one-way distance in ft) ÷ circular mils  ·  K = 12.9 for copper, 21.2 for aluminum  ·  Drop % = drop ÷ supply voltage × 100  ·  Guideline: keep branch-circuit drop at or under 3%

Solved example

20 A over 100 ft at 240 V on 12 AWG copper: (2 × 12.9 × 20 × 100) ÷ 6,530 = 7.90 V of drop = 3.29% — over the 3% guideline. Stepping up to 10 AWG brings it to 4.97 V (2.07%).

FAQs

What voltage drop is acceptable?

3% on a branch circuit is the common design target (5% total for feeder plus branch). It is a guideline, not a hard code rule — this calculator flags anything over 3% and names the smallest wire size that fixes it.

Why is the same wire worse at 120 V than at 240 V?

The drop in volts is identical — 20 A over 100 ft on 12 AWG copper loses 7.90 V either way — but at 120 V that is 6.58% of the supply, versus 3.29% at 240 V. The percentage is what lights and motors actually feel.

Does this replace an electrician?

No — voltage drop is only one check. Ampacity (the breaker protecting the wire), insulation temperature rating and local code also decide the size, and a licensed electrician should verify any real installation.