Home › Duct Size Calculator
Duct size for an airflow — the round diameter you need, the standard size to actually buy, and the rectangular ducts that match it.
No cost line here — this one is geometry / sizing, not a material quantity. Cost depends on the material and installer you choose.
Required area (sq ft) = airflow (CFM) ÷ velocity (FPM) · Exact round diameter (in) = 2 × √(area ÷ π) × 12 · Recommended size = the next standard round size up · Actual velocity = CFM ÷ the recommended size's area
1,000 CFM at a 900 FPM target: 1,000 ÷ 900 = 1.11 sq ft of duct area — an exact round diameter of 14.3 in, so the recommended standard size is 16 in round, where the air actually slows to about 716 FPM.
For residential supply ducts, about 700–1,000 FPM is the usual design range — this calculator defaults to 900. Return ducts are typically designed slower, around 600–700 FPM, because they sit closer to the living space and noise carries.
Ducts come in fixed sizes, so you round up to the next one — and a bigger duct carrying the same airflow moves that air more slowly. Slower is quieter and loses less to friction, so rounding up is the safe direction; rounding down makes the system loud and starves the room.
No — it sizes one duct run for a given airflow. A full system design (Manual D) also adds up friction loss over the longest run, the fittings and the blower's available static pressure. Use this for single-run sizing and sanity checks.