Home › Conduit Fill Calculator
How full is that conduit? Total wire area and fill percentage for up to three THHN wire sizes, checked against the NEC fill limits.
No cost line here — this one is geometry / sizing, not a material quantity. Cost depends on the material and installer you choose.
Fill % = total conductor area ÷ conduit internal area × 100 · NEC Chapter 9, Table 1 limits: 1 wire = 53% · 2 wires = 31% · 3 or more wires = 40% · Conductor areas are the approximate THHN areas from NEC Chapter 9, Table 5
Three 12 AWG THHN wires (0.0133 sq in each) in ½ in EMT (0.304 sq in of internal area): total conductor area 0.0399 sq in = 13.1% fill — well under the 40% limit for 3 or more wires. At that 40% limit, the same conduit could hold up to 9 of those wires.
Two wires pulled side by side can jam against each other and the conduit wall at bends, so Table 1 holds 2-wire runs to a lower fill. A single wire gets 53% because there is nothing to jam against; three or more wires settle into the space and are allowed 40%.
Yes — every conductor in the conduit counts, including equipment grounding conductors. Add them as one of the wire groups above.
No — they are the approximate THHN areas from NEC Chapter 9, Table 5. Conductor types vary (THHN, XHHW, compact strand, bare), so check the printed specs on the actual wire for a final design — and a licensed electrician should verify any real installation.