Conduit Fill Calculator

How full is that conduit? Total wire area and fill percentage for up to three THHN wire sizes, checked against the NEC fill limits.

Type your numbers — the result updates live.

No cost line here — this one is geometry / sizing, not a material quantity. Cost depends on the material and installer you choose.

Formula

Fill % = total conductor area ÷ conduit internal area × 100  ·  NEC Chapter 9, Table 1 limits: 1 wire = 53% · 2 wires = 31% · 3 or more wires = 40%  ·  Conductor areas are the approximate THHN areas from NEC Chapter 9, Table 5

Solved example

Three 12 AWG THHN wires (0.0133 sq in each) in ½ in EMT (0.304 sq in of internal area): total conductor area 0.0399 sq in = 13.1% fill — well under the 40% limit for 3 or more wires. At that 40% limit, the same conduit could hold up to 9 of those wires.

FAQs

Why is the limit lower for 2 wires (31%) than for 3 or more (40%)?

Two wires pulled side by side can jam against each other and the conduit wall at bends, so Table 1 holds 2-wire runs to a lower fill. A single wire gets 53% because there is nothing to jam against; three or more wires settle into the space and are allowed 40%.

Do ground wires count toward conduit fill?

Yes — every conductor in the conduit counts, including equipment grounding conductors. Add them as one of the wire groups above.

Are these conductor areas exact?

No — they are the approximate THHN areas from NEC Chapter 9, Table 5. Conductor types vary (THHN, XHHW, compact strand, bare), so check the printed specs on the actual wire for a final design — and a licensed electrician should verify any real installation.